Fire-Lite BG-12 & MS-Series: Specs, Listings, and the Permit Path

The pull station and the panel it reports to — DF- data sheet numbers (including the two everyone crosses), CSFM listing path, and the calculations the package cannot ship without.

PermitsPros is a California and nationwide permit expediting firm specializing in building permits and fire protection. Since 2008. One page for the two Fire-Lite searches that arrive together: the BG-12 pull station going on the plans, and the MS-Series panel it reports to.

The BG-12 family, from data sheets DF-52004 and DF-52013

Fire-Lite's BG-12 series is its manual pull station line — non-coded stations in single- and dual-action versions, with hex-lock and key-lock models. The conventional stations are covered by data sheet DF-52004; the addressable BG-12LX has its own sheet, DF-52013.

The MS-Series panels, from their DF- data sheets

The California listing path

Fire-Lite equipment files in California under the State Fire Marshal's Building Materials Listing program. The BG-12 family's CSFM listing is 7150-0075:0184 (category 7150, manual stations), printed on the data sheets' own agency listings next to UL/ULC S711. The panel sheets print their CSFM numbers too — 7170-0075:217 on the current MS-9600LS/UDLS sheet (an older revision's appended listing page shows a differently formatted number, which is why the revision you cite matters) and 7165-0075:210 for the MS-9050UD. Every listing carries an expiry and is revised on the program's cycle, so the sheet in the package must be the current one; "Provide current CA SFM Listing" is a correction our desk has carried back from a California reviewer this year, in substance word for word.

What the submittal package needs for this family

The permit path

Pull stations and panels ride the project's fire alarm permit, reviewed by the fire prevention division or district. A panel replacement is plan-review work — the heaviest routine job in the alarm family — while adding or moving stations rides the same permit. Thresholds for minor work vary by jurisdiction. PermitsPros assembles the package, files it, carries corrections, and delivers the issued permit: $250 filing service or $495 complete package; city and district fees separate. Start at portal.permitspros.com or call (888) 907-9511.

Spec facts on this page are drawn from Fire-Lite's own published data sheets, cited by DF- document number and revision. Two data-sheet numbers in circulation for this family are easy to cross: DF-60334 is the MS-9600LS sheet and DF-52418 is the MS-9050UD sheet — they are different panels, and the sheets are not interchangeable. Where a data-sheet revision changes a printed listing number, this page says so.

Questions and answers

Q: What is the difference between the BG-12 models?

A: From Fire-Lite data sheets DF-52004 (conventional) and DF-52013 (addressable): the single-action stations are the BG-12S (pigtail connections, hex lock) and BG-12SL (key lock). The BG-12 is dual-action; the BG-12L is the BG-12 with a key lock; the BG-12LPS is the dual-action station with a pre-signal feature; and the BG-12LX is the addressable dual-action station — it carries an addressable interface inside, reports its exact point to the panel, and is key-reset. The suffix is not decoration: an addressable -LX and a conventional station are different devices on the plans and in the listing.

Q: What data sheets cover the Fire-Lite MS-Series panels?

A: Fire-Lite publishes them by DF- number: MS-9600LS / MS-9600UDLS is DF-60334; MS-9050UD is DF-52418; the conventional MS-5UD-3 and MS-10UD-7 share DF-52416; the MS-25 is DF-60702. A submittal cites the sheet for the panel actually on the device schedule — DF-60334 and DF-52418 are routinely confused, and they describe different panels.

Q: How many devices do the MS-Series addressable panels support?

A: Per the data sheets: the MS-9600LS runs one SLC loop with up to 318 addressable devices — 159 detectors plus 159 modules — and an optional SLC-2LS expander adds a second loop, for up to 636 devices fully loaded. The MS-9050UD supports up to 50 addressable devices of any type on its single loop. Those capacities are what the loop and device-count sections of a submittal are checked against.

Q: What listing evidence does an MS-Series panel submittal need in California?

A: The panel's data sheet (its DF- number), the current California State Fire Marshal Building Materials Listing sheet for the exact panel model — the numbers printed on the current data-sheet revisions include CSFM 7170-0075:217 for the MS-9600LS/UDLS and 7165-0075:210 for the MS-9050UD — and the calculations: standby battery calculations and NAC voltage-drop calculations sized to the loads on the panel's data sheet. Where monitoring is in scope, the communicator's paperwork rides the same package: the MS-9600UDLS ships with a factory-installed DACT-UD2, and the MS-9050UD carries an integral DACT.

Q: What is the BG-12's California listing?

A: CSFM 7150-0075:0184, category 7150 (manual stations) — printed in the agency listings on the data sheets themselves (DF-52004 and DF-52013), alongside UL/ULC listing S711 and UL 38 compliance. Listings are revised and expire, so the sheet pulled for a submittal is checked for currency at filing time — the current sheet is the one reviewers accept.